This test is a rolling bend test. The cable assembly is clamped near the start and end of the bend.
All assemblies were terminated with AMP Cat 6 modular plugs. All assemblies were tested using a FlukeĀ® hand held tester with patch cord adapters. Cat 6 limit lines were used so that performance changes would be more visible.
Two tests each were done on 4 pair Quabbin part number 5752 and 2 pair Quabbin part number 5772 IE patch cable assemblies. The first test was a 1 million cycle test and the second was a 10 million cycle test.
All testing was done in a heated warehouse space. Temperatures ranged from 15C to 35 C. Humidity was uncontrolled and not measured.
Cables were clamped using 4 bolts through a plate at each end of the flex stroke. Foam polyurethane was used to prevent damage to the cable and to provide strain relief at the clamp point.
view complete test results at www.quabbin.com