2MW Diesel Generator Test
Loading...
12,533
Loading...
Uploader Comments (bdosborn)
see all
All Comments (13)
-
all I have to say about the failure pictures is Houston We Have a Problem.
-
1:40 the best generators there are ATLAS COPCO QAS338
-
look like fun, I used to work for that company
-
I have 4 x 11kv 1.25Mva sets at my work place. I hope they dont do this!!!
Loading...
In a commercial application is there a way to test the functionality of a ATS without affecting the critical load?
JCAUPS1 2 weeks ago
Yes, get a closed transition transfer switch. Its a make-before-break transfer so you can switch loads without a bump.
bdosborn 2 weeks ago
What caused the failure in the 1st place?
ah0386 4 months ago
Never found out why. It was a brand new alternator too.
bdosborn 3 months ago
thats a serious gen set, is it a 400 volt set?
bobbj77 6 months ago
480V
bdosborn 6 months ago