fire pump with generator test
Loading...
9,078
Loading...
Uploader Comments (twoplyboy)
see all
All Comments (21)
-
@twoplyboy Fair play. Also adam900r is mistake. Inlet piping is fine.
-
@martylaurie This is correct. The inlet piping is fine. You need 10 pipe diameters before you can elbow horizontally. But because the 90 goes up, it's fine.
-
Not to code ?
Read the new standard, vertical change of direction is fine.
Good test, packings leaking and higher PSI gauges are needed.
-
can you explain....
please
-
can you please explain....
-
@silvafaedo 10 pipe diameters only applies to horizontal elbows, not vertical.
-
you should see the fire pumps on naval ships, i saw the motor on one, it was rated at 115hp!!
-
The suction has a elbow, less 10 diameter distance
Loading...
Wrong gauge on pump discharge - deduct 120 points for Hufflepuff
ltm0011 7 months ago
@ltm0011 it was like that. it was our first time here. so technically I shouldn't lose any points cuz we didn't place it on the pump in the first place!
twoplyboy 7 months ago
this install is not to code,check the inlet piping.
adam900r 1 year ago
@adam900r please explain.
twoplyboy 1 year ago
Very nice., sounds good.
If I may ask, what is a garbage chute inspector's test?
Natesmodelrailroad 2 years ago
it's a test point that we use to flow water to simulate a sprinkler flow in the garbage chute.
twoplyboy 2 years ago