fire alarm system 4 wire smoke detector hook up
Uploader Comments (Federal3t22)
Top Comments
-
What is the difference between 4 wire and 2 wire? Which is better?
-
good quality
All Comments (45)
-
how do you get rid of faults iv wired it up but it haqs no batterys the error im getting is pcu fault & psu fault and when i try mute panel it does not mute any ideas ?
-
@Federal3t22 I''ve got a video fo hooking up a DC alarm to a pull coming soon
-
@HalomasterA69 h t t p:// w w w .y o u t u b e .c o m / watch?v=-gwUD_DHzJk this should help.
-
@Federal3t22 Hey,how do i wire up a pul station and a simple horn/strobe ?
-
@mrxexellent The EOL should be placed at the detector that is at the very end of the loop. The EOL could be placed in parrallel at the panel but that would negate any fault monitoring of the field detectors and cabling.
-
@Federal3t22 OK thanks verry much!
What's the price of that panel????????
indigo4fox 10 months ago
@indigo4fox depending on condition, you can find them from as low as $100 with just the circuit board with components missing, to as high as $400 new in the box.. I got this one for around $150 back in 2005,so with inflation, I'd say it would cost around $250 now. But be warned, these panel go fast as other collectors, and parts dealers (especially 2 particular ones) snap them up fast for re-sale (they usually jack the prices up sky high)
Federal3t22 10 months ago
whats the voltage used
thingyee1118 10 months ago
@thingyee1118 24VDC full wave rectified
Federal3t22 10 months ago