Uploader Comments (GreenDreamGroup)
All Comments (12)
-
Why do you drill the first hole in the furnace? Was that before you realized it was mechanically assisted? Thanks - great videos
-
Great, concise explanation of CAZ BPI Testing protocol.
-
This is Great! Thanks for the Info!
-
@baikoff Hope this helps. BPI standards allows to drill through a power-vent Furnace if the FLUE is single wall only. If is a DOUBLE WALL FLUE to vent the furnace in some states you are not allowed to drill though a VENT FLUE. And regarding your second question regarding why test for draft on a POWER-VENT furnace??? The answer is that you are making sure that the FAN is working like is suposed to work. If is not working at all, it may fail the draft test.
-
I think the video was not complete I wanted to see the full test and readings I am taking the BPI test in two weeks
Ok - I'm confused. Wouldn't the first hole cause worse dilution? I don't recall making 2 holes as standard bpi protocol?
sienalaurel 3 weeks ago
@sienalaurel This is actually a mistake commonly made in the field- CO must be measured prior to dilution air, and draft must be measured 1-2 ft past the draft diverter or first elbow, in a straight section of the flue. That's usually 2 different holes, and lots of technicians are using tools that do both jobs with one probe, which they assume means only 1 hole. If you sample both 1-2 feet past the draft control, the CO is wrong, and if you sample both before dilution, the draft is wrong.
GreenDreamGroup 3 weeks ago
Actually, since the CO sampling should be before any dilution air, you want to get as close as possible to the heat exchanger-- there are some small gaps in the joints between the flue components, and since the inside of the flue is at a negative pressure, it will suck air into the flue, resulting in 'dilution' of the flue gases. That's the reasoning for the lower of the two holes. You would NOT measure draft there, though, since there may be positive pressure lingering from the inducer.
GreenDreamGroup 3 weeks ago
When testing for Carbon monoxide in step two how many ppm is acceptable?
TheDIYContractor 1 month ago in playlist More videos from GreenDreamGroup
@TheDIYContractor For BPI, 25 ppm is the max acceptable in the flue, 35 ppm is the max acceptable in the air around you. 100 ppm or more, and the issue needs to be taken care of before other work in the house is tackled.
GreenDreamGroup 1 month ago in playlist Combustion Testing