Commercial Electrical Load Calculation-NEC-U#11-01-12-13-10.wmv

Loading...

Sign in or sign up now!
Alert icon
Upgrade to the latest Flash Player for improved playback performance. Upgrade now or more info.
9,186
Loading...
Alert icon
Sign in or sign up now!
Alert icon

Uploaded by on Jan 10, 2011

Sizing Electrical service for a commercial building using NEC.

Category:

Education

Tags:

License:

Standard YouTube License

  • likes, 0 dislikes

Link to this comment:

Share to:
see all

All Comments (6)

Sign In or Sign Up now to post a comment!
  • @Lookingforwardish 1.25 is the multiplier for continuous loads which are loads that run for 3 hours or more. In this case, general lighting is a continuous load hence the multiplier of 125% for the conductor and overcurrent protection

  • what language is this?

  • good Job

  • Yet I see you used Volt amps for Lighting and multiplied the entire result by 1.25. In so using volt amps you would have increased volts by 1.25 and amps by 1.25. Would doing it this way create a problem of oversizing the cable. I suppose being larger than required is up to code as you exceed minimum standard.

  • My question is about your 125% multiplier. When is it best to use the 125% increase for wire sizing? I took 2 master electrician exams in two states and both states I left this off until it was needed for wire sizing. The result is the final solution is correct in both cases but the exams in one state differed from the other state. One state must be using what you do. While the other does the loads (such as 3.5va x sq. ft= A.) with no 25% increase until the final cable sizing.