Hello Dr.Z,thanks for the followup ....I replaced the thermostat..Problem fixed...
-
@MrTERRYD55 Just curious what did you eventually find wrong with your unit?
-
This smart ass took six minutes to tell me what he could have in 30 seconds. I don't care what he had for lunch and I don't want to hear the whack it with a hammer fix. I wouldn't call this yahoo to do anything for me.
-
great job. love you viedos keep it up . learning havac your viedos have realy realy helped , THANKS
Loading...
haha just saw the vid uncle jim
Hi me!
Eiekk 11 months ago
@Eiekk Thanks. I hope that you liked it.
DrZarkloff 11 months ago
i use sunday paper to beat my dog , who knew it had so many uses. I love recycling
waters65 1 year ago
@waters65 lol
DrZarkloff 1 year ago
Dr.Z........got a good for you..........Goodman gas package unit has locked out/shut down.......Replace c/b...transformer,contactor,capacitor,I do not have 24 volt at the contactor-coil.The evap.motor does run on the fan side of the thermostat.but nothing else.There is 33.4 volts on the secondary of the transformer.Check all f/s,r/s,l/s.I even wired the thermostat at the molex plug directly......still nothing .What am I missing..........
MrTERRYD55 1 year ago
@MrTERRYD55 You might want to try jumpering the red thermostat wire to the green wire and see if the fan comes on. If it does then there's something wrong with the thermostat or the wire going to the thermostat.
DrZarkloff 1 year ago