A/C Liquid Line Noise (Hissing) - Goodman 3-ton (Part 1)

Loading...

Sign in or sign up now!
Alert icon
Upgrade to the latest Flash Player for improved playback performance. Upgrade now or more info.
2,944
Loading...
Alert icon
Sign in or sign up now!
Alert icon

Uploaded by on Aug 8, 2010

Video I took about 3 months after an evaporator coil swap (due to leaks in original coil). System is less than 2 yrs old, but started making a hissing noise in the high pressure LL after the new coil was installed. Superheat & subcooling are on target. Contractor says everything is fine, what do you think?

Links to discussions about this issue:

My post:
http://hvac-talk.com/vbb/showthread.php?t=545652

Other posts:
http://hvac-talk.com/vbb/archive/index.php/t-79008.html
http://hvac-talk.com/vbb/showthread.php?t=75849
http://hvac-talk.com/vbb/showthread.php?t=142187

Category:

Education

Tags:

License:

Standard YouTube License

  • likes, 1 dislikes

Link to this comment:

Share to:

Uploader Comments (ljbrandt500)

  • I was trying to figure out the noise that was coming out of my AC line when I found your video. I'm having the exact same issue with a 2.5 ton goodman installed in Jan 2009. I had the exact same experience with the contractor that installed mine. They said everything is OK and the sound is normal. Still... they couldn't explain the cause.

  • @cassini83 If you ever find out what it is or fix it, please don't hesitate to post back here, thanks!

  • UPDATE 4/30/2011 - Just wanted to let everyone know that I haven't had any work done on the system since the video was taken and I'm still hearing the same noise this cooling season. However, I thought I'd mention one new thing I've noticed; the hissing/gurgling noise goes away when the inside air temperature is 74 deg or above. The hissing doesn't "kick-in" until the system starts cooling the house 73 deg and below. At 73 degrees it's intermittent and @ 70 deg, the hissing is constant Ideas?

  • Scratch that...the hissing now persists (albeit intermittently) no matter what the indoor temp is.

  • A 'hissing' liquid line may indicate undercharge. Hard to say. Could be noncondensibles (air/moisture) in the system or a restriction (maybe at the internal line drier inside the unit). I've never been a fan of units with line driers in the outdoor section. Kinda weird to see a new liquid line installed on the exterior. I've never run just a single new refrigerant line. I replace both the suction and liquid lines if there's a doubt about either of them. Better to be safe than sorry.

  • @PutSome5tankOnIt Thanks for your advice! BTW- I really enjoy watching your videos, very informative and entertaining! I finally found a great contractor locally, who would be able to fix it i.e. increasing return air filter surface area to proper specs, setting proper fan speed and verifying air-flow, replacing & relocating filter drier and triple evac/recharging system for about $1500. They also said they would double check the piston/flow-rator for correct sizing and seating. Worth it?

see all

All Comments (24)

Sign In or Sign Up now to post a comment!
  • when a tech hooks up his gauges to check pressures, see if the needles are floating back and forth. If they are then you have non condensables in the system!

  • If it was not hissing before the coil change out, then either the piston is wrong size but that is the less likely if the contractor got the replacement coil from Goodman under warranty. It sounds like the tech left moisture in the system or did not purge with nitrogen as he was soldering in the new coil which would put non condensables in the system. Also listen to the contractor that said to add a return, (he checked your systems cfm) it will add life to your system!

  • I had a similar thing happen but it was a hissing coming from the compressor and it was like it was releasing pressure. It also caused a terrible rattling noise inside the house too. Later discovered it was the seal going out and I replaced compressor cleaned out the lines and it was good to go.

  • If the liquid line is cold to the touch probably non condensables. Is your subcooling high?

    Would be nice to have a sight glass on that liquid line.

  • @ljbrandt500 Absolutely! BTW here's the model numbers of my equipment (all installed at the same time)

    Furnace/blower - GKS90703BXAD

    coil - CAPF1824B6CA

    A/C - GSC130241AD

  • @ljbrandt500 WOW! You watch my videos? COOL!!!!

    I'm a company kind of guy but this economy is bad for everyone. The contractor you found seems to be willing and able to do your system right for you. Fifteen hundred is a lot of scratch to dig out of your pocket to fix a problem that the original installer should have done properly in the first place.

    You didn't hear this from me... but...

    Ask for a TXV to be installed at your indoor coil... free of extra charges.