Glad we are all mature here. Good job on the Amerex install guys. We are 20 mins from the factory and we've had a wobderful relationship with them since they made their first dry chem hand held.
Everything looks good but no vent check on actuation. Yep 2-14178 will do the job and will keep it at 4 flow. The guy talking about Ansul links and nozzles needs to get a job doing something else if he can't determine nozzles. Maybe when ge moves out of keeping inventory he will get some field experience.
@coldfiresoutheast Yeah theres no vent check at the moment. but as soon as we take the test bottles down. I promise you the vent plug will be present. Thanks for your concern.
Ansul link housings and nozzles on the Amerex Kings Amerex system. This is a pre-piped hood for Anusl and they installed Amerex tanks. This is a non compliant system!!!!! You guys screw someone.
Well you have one drop it looks like for 6 burners....Amerex only allows you 4 flow points per drop....this range will take 3 flow points regardless if you use 3 of the 11982 nozzes for each 2 eye section or what. If you had 2 drops you could use a 14178 nozzle to cover the first 4 eyes and then you could use 1 11982 to cover the remaining 2 eyes. That's per the book. The system would be non compliant if I walked in to service it due to it's not properly protecting the range per the book.
Very true on the number of flows on a single drop...this range is covered with 2 x 14178 on a single drop, centered in two seperate 4 burner modules, which is very much compliant. In this scenario the center two burners are double covered.
What is your nozzle to grease distance on this fryer hood to your nozzles? Unless you got some good distance your 13729 isn't going to work, you'd have to use a few 11982s to get some low prox coverage on a hood like that...>Capt D's is a prime example of what I'm talking about? Did you use (2) 14178 nozzles over the range or did you mix a 14178 with an 11982? Where is your vent check on your actuation line, it may have been behind the far left bottle on the back of the T...couldn't see it.
The exhaust fan is running. The fresh air is on, while cooking. Then the system dumps and the fresh air turns off, the exhaust stays running to suck out smoke. Did that answer your question?
@RamAir02TA77 All brands,really.From ansul to pyro-chem,kidde,range guard,badger,buckeye,saftey first.But the best most expert well engineered system is Amerex!
Glad we are all mature here. Good job on the Amerex install guys. We are 20 mins from the factory and we've had a wobderful relationship with them since they made their first dry chem hand held.
coldfiresoutheast 11 months ago
Everything looks good but no vent check on actuation. Yep 2-14178 will do the job and will keep it at 4 flow. The guy talking about Ansul links and nozzles needs to get a job doing something else if he can't determine nozzles. Maybe when ge moves out of keeping inventory he will get some field experience.
coldfiresoutheast 11 months ago
@coldfiresoutheast Yeah theres no vent check at the moment. but as soon as we take the test bottles down. I promise you the vent plug will be present. Thanks for your concern.
daverod707 11 months ago
Nice try on the Ansul link brackets...Ansul are only about 8 inches long, these are definately longer than that...
Another nice try on this being a pre-piped hood, and how would you know if it was pre-piped for Ansul or any other system?
Annnnndddddd, how could you possibly tell if they are Ansul nozzles or Amerex from this video?
Nice try all around, Amerex King stands!!!
kbtiii 11 months ago
This has been flagged as spam show
Ansul link housings and nozzles on the Amerex Kings Amerex system. This is a pre-piped hood for Anusl and they installed Amerex tanks. This is a non compliant system!!!!! You guys screw someone.
smsharrock1 11 months ago
Comment removed
smsharrock1 11 months ago
@smsharrock1 comment FAIL.......................
TheZekerod 11 months ago
Well you have one drop it looks like for 6 burners....Amerex only allows you 4 flow points per drop....this range will take 3 flow points regardless if you use 3 of the 11982 nozzes for each 2 eye section or what. If you had 2 drops you could use a 14178 nozzle to cover the first 4 eyes and then you could use 1 11982 to cover the remaining 2 eyes. That's per the book. The system would be non compliant if I walked in to service it due to it's not properly protecting the range per the book.
coldfiresoutheast 11 months ago
@coldfiresoutheast ...
Very true on the number of flows on a single drop...this range is covered with 2 x 14178 on a single drop, centered in two seperate 4 burner modules, which is very much compliant. In this scenario the center two burners are double covered.
kbtiii 11 months ago
@coldfiresoutheast well can you service these nutts!!!!
TheZekerod 11 months ago
What is your nozzle to grease distance on this fryer hood to your nozzles? Unless you got some good distance your 13729 isn't going to work, you'd have to use a few 11982s to get some low prox coverage on a hood like that...>Capt D's is a prime example of what I'm talking about? Did you use (2) 14178 nozzles over the range or did you mix a 14178 with an 11982? Where is your vent check on your actuation line, it may have been behind the far left bottle on the back of the T...couldn't see it.
coldfiresoutheast 1 year ago
What's the best way to cover 6 burner?
I mean of course what nuzzles should I use...
mcafri 11 months ago
@coldfiresoutheast if it were an ansul system and the test was done on a minday could you see these nutts!!!!
TheZekerod 11 months ago
The exhaust fan is running. The fresh air is on, while cooking. Then the system dumps and the fresh air turns off, the exhaust stays running to suck out smoke. Did that answer your question?
daverod707 1 year ago
wheres your automatic fan activation?
jayda997 1 year ago
What other brands do you install?
RamAir02TA77 2 years ago
@RamAir02TA77 All brands,really.From ansul to pyro-chem,kidde,range guard,badger,buckeye,saftey first.But the best most expert well engineered system is Amerex!
daverod707 2 years ago
The sound scared the hell outa me!
chazzrod14 2 years ago